Are you preparing for a Circuit Breaker job interview? Then you are at the right place for getting good interview questions that can land your dream job. Circuit Breaker is a mechanical piece of equipment designed to open or close contact members, thus opening or closing an electrical circuit under the standard or non-standard conditions. People seeking Circuit Breaker jobs should be skilled in Isolators, PTS, CVT, Relays, LT Transformers, Power Transformers, Insulators etc. Circuit Breaker experts are placed in top positions like Electrical Site Engineer, Electrical Project Engineer, Electrical Maintenance Engineer, Electrical Supervisor, Electrical Technician, Shift Engineer, Service Engineer, Test Engineer etc. To know more about Circuit Breaker interview Questions please visit our Circuit Breaker job interview questions and answers page designed by wisdomjobs professional experts.
Question 1. What Is A Circuit Breaker?
Answer :Circuit Breaker is a mechanical device designed to close or open contact members, thus closing or opening an electrical circuit under the normal or abnormal conditions.
Question 2. How Does A Circuit Breaker Different From Switch?
Answer :Switch is just a device when can be able to open and close the circuit during normal operation. Whereas on the other hand circuit breaker has the ability to open and close the contacts during abnormal or fault conditions. Thus circuit breaker has the potential to break and make heavy short circuit currents. Auto-reclosures in the circuit beaker has the ability to re-close after certain designed duration to verify whether the short circuit was cleared.
Question 3. What Is Meant By Making Capacity Of The Circuit Breaker?
Answer :The making capacity of the circuit breaker when closed on a short circuit is the peak value of the maximum current wave (including dc component) in the first cycle of the current after the circuit is closed by the circuit breaker.
Question 4. Why Current Chopping Is Not Common In Oil Circuit Breakers?
Answer :Current chopping is not common in oil circuit breakers because in most of the oil circuit breakers the arc extinguishing power is proportional to the magnitude of current to be interrupted.
Question 5. Name The Materials Used For The Contacts Of Vacuum Circuit Breakers?
Answer :Copper-Bismuth, Copper-lead, Copper-tellurium, Silver-bismuth, Silver-lead and Silver-tellurium are some of the alloys employed as contact materials in the vacuum circuit breakers.
Question 6. Why Current Chopping Considered As Serious Drawback In A Circuit Breaker?
Answer :The current chopping is considered as serious drawback because it sets up high voltage transient across the breaker contacts.
Question 7. For Ehv Applications Which Type Of Circuit Breaker Is Mostly Preferred?
Answer :For Exta High Voltage (EHV) applications SF6 gas insulated switchgear is preferred.
Question 8. What Are The Duties Of Circuit Breakers?
Answer :
Some of the duties of the circuit breakers are listed below:
Question 9. What Is The Meaning Of Rupturing Capacity Of A Circuit Breaker?
Answer :
Rupturing capacity of a circuit breaker means the maximum power a circuit breaker can interrupt under a fault. It is usually expressed in Mega volt Ampere (MVA) and it is then the product of the rated breaking current in kilo amperes and rated voltage expressed in kilo volts.
Answer :
Answer :
“Short Circuit MVA” is the rupturing capacity or breaking capacity of a circuit breaker in case of a three phase symmetrical fault which determines the size of the circuit breaker. The breaking capacity of a circuit breaker is specified either in terms of symmetrical breaking current/MVA or asymmetrical breaking current/MVA.
Answer :
To select the MVA rating of the circuit breaker of a high voltage installation the fault level at the incoming point of supply must be known. Power supply authority furnishes the fault level.
Question 13. In What Value The Making Current Of A 3-phase 3000 Mva, 33 Kv Breaker?
Answer :
the making current is normally specified in peak value.
Breaking current = 3000/(√3×33) KA = 52.48 KA
Making current = 2.55 × 52.48 = 133.82 KA.
Question 14. What Do You Mean By “asymmetrical Breaking Current” And “symmetrical Breaking Current”?
Answer :
The asymmetrical breaking current is the r.m.s. the value of the total current at the initial instant of contact separation and is equal to the square root of the sum of the squares of the symmetrical breaking current and of the direct component of the current at the same instant. The symmetrical breaking current is the r.m.s. the value of the symmetrical current (a.c. component of current) at the initial instant of contact separation. Actually, the rating of the breaker is specified in terms of symmetrical breaking current & voltage.
Answer :
As the symmetrical fault is most severe in a three phase line and imposes the heavy duty on the control gear, therefore, the circuit breaker is rated on the basis of symmetrical short circuit currents.
Question 16. Why Is Symmetrical Fault More Severe Than The Unsymmetrical Fault In A 3-phase System?
Answer :
In a symmetrical fault since all the three conductors are short circuit together causing equal fault currents to flow through the line then the symmetrical fault because more severe.
Question 17. What Is The Importance Of Base Kva In Short Circuit Calculations?
Answer :
As the various equipment used in the power system have different KVA rating with different percentage reactances so for easy calculation it is necessary to find the percentage reactances of all equipment on a common KVA rating. This common KVA rating is known as base KVA.
Question 18. Does The Value Of Short Circuit Current Vary For Different Values Of Base Kvas?
Answer :
No. Whatever may be the value of base KVA the value of short circuit current remains unchanged.
Question 19. What Do You Mean By The ‘recovery Voltage’ Of A Circuit Breaker?
Answer :
The recovery voltage is defined to be the r.m.s. the value of the line voltage of service frequency that reappears across the poles of the circuit breaker short after arc extinction in all the poles and after damping of the transient phenomena.
Question 20. What Do You Mean By The Term ‘restriking Voltage’ Of A Circuit Breaker?
Answer :
The restriking voltage or the transient recovery voltage is the voltage between the contacts of a pole of the circuit breaker after the extinction of the arcs while the transient state persists.
Answer :
As the voltage rating of circuit breaker corresponds to highest system voltage so the circuit breaker to be used on 6.6 kV line should be of rated voltage 7.2 kV and so on.
Question 22. On What Factors Does The Rate Of Rising Of Restriking Voltage Depend?
Answer :
The rate of rising of restriking voltage depends upon the inductance and capacitance of the system.
Question 23. Why Is Current Interruption Easier In An A.c. Circuit Than In A D.c. Circuit ?
Answer :
Due to natural current zeros in alternating current waves interruption of an a.c. circuit becomes more easier.
Question 24. Is An A.c. Circuit Breaker Suitable For D.c. Supply Line?
Answer :
Generally a.c. the circuit breaker is not suitable for d.c. supply line because of a.c. circuit breaker quenches arc easily at current zero of an alternating wave which is not possible in d.c. due to nonexistence of current zero.
Answer :
(a) It is possible only when the breaker is type tested at 60 Hz frequency, otherwise not.
(b) A 12 kV circuit breaker can use for any voltage up to its rated voltage under the condition that the breaking current is within its breaking capacity.
Answer :
Question 27. How Are The Rating Of A Circuit Breaker Given?
Answer :
The rating of a circuit breaker are given by